O²T/FSp multisensor fire detector IQ8Quad with isolator, customized version

802385.SV99

Approval: VdS

O²T/FSp multisensor fire detector IQ8Quad with integrated flasher, sounder and speech

As 802385, but with individual text and/or sounds. The max. recording time per device is 169 seconds.

  • Detection
  • The reliable O²T multisensor principle for consistent response performance at the highest level of security against false alarms
  • Individual control of the sounder and beacon
  • Tones can be used for other purposes in addition to warning of fire, making the device ideal for use in schools etc.
  • Soft start option, ideal for hospitals and nursing homes
  • Flash lamp
  • Loop powered - no need for external power supply
  • No additional short address
  • Automatic synchronization of various IQ8Quad alarm signaling devices
  • High flash energy
  • Sounder
  • Loop powered - no need for external power supply
  • No additional short address
  • Automatic synchronization of various IQ8Quad alarm signaling devices
  • Maximum sound level: 92 dB (A) at 1 m
  • Maximum sound pressure can be set
  • Multiple signal components can be combined to one signal template
  • Signal template and repetition rates can be set
  • Up to 26 different languages are available
  • 20 different signal tones, incl. DIN-tone
  • Low power consumption
  • Speech message with sounder
  • Loop powered - no need for external power supply
  • No additional short address
  • Automatic synchronization of various IQ8Quad alarm signaling devices
  • Maximum sound level: 92 dB (A) at 1 m
  • Maximum sound pressure can be set
  • Multiple signal patterns can be combined to one signal
  • Signal pattern and repetition rates can be set
  • 20 different signal tones, incl. DIN-tone
  • Speech messages can be played in up to 5 languages
  • 5 alarm messages per languages are preprogrammed
  • Up to 26 different languages are available


Additional Information:

When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" and fill in “Order form for individual combination of languages”.
Costs for the recording of customer-specific texts and/or tones can be obtained by request.
Cancellations or returns are not possible.
Not suitable for application in detector base Part No. 805591!

Scope of Delivery:

Programmed according to customer specifications.
Application temperature-20 °C ... 65 °C
Operating voltage8 ... 42 V DC
Colorwhite, similar to RAL 9010
Weight gapprox. 145 g
Storage temperature-25 °C ... 75 °C
Load factor3
Air velocity0 ... 25.4 m/s
MaterialABS plastic
Air humidity< 95 % (non-condensing)
Quiescent current @ 19 V DCapprox. 90 μA
Quiescent current @ FACP batteryapprox. 500 μA @ 42 V
Type of protectionIP43 (with base + options)
Area to be monitoredmax. 110 m²
Height to be monitoredmax. 12 m
Dimensionsø: 117 mm H: 67 mm (incl. base)
  • 767800 Mounting bracket
  • 805590 Standard detector base for IQ8Quad