IQ8MCP electronic module with isolator

804905

Approval: VdS, CNBOP

Addressable electronic module suitable for use in the esserbus and powered loop with alarm latch and alarm indicator. Optional connection for conventional manual call point. Without BUS connection, the detector operates as conventional manual call point. Built-in loop isolator in the manual call point.

CNBOP certificate valid only with additional “Pozar” sign available as option (Part No. 704911).
Additional Information:
Take note, for a LARGE MCP you have to order the electronic module and the MCP housing separately to have a complete MCP.
Alarm displayLED, red
Alarm current w/o communication curtainapprox. 18 mA
Connection terminalmax. 2.5 mm² (AWG 26-14)
Application temperature-20 °C ... 70 °C
Operation indicatorLED, green
Operating voltage8 ... 42 V DC
HousingPC ASA plastic
Weight gapprox. 236 g (in housing)
Storage temperature-30 °C ... 75 °C
No. of detector/zone10 detectors per zone, 127 detectors/loop (according to VdS)
Detector specificationEN 54-11, type B
Air humidity< 95 % (non-condensing)
Quiescent current @ 19 V DCapprox. 45 μA
Type of protectionIP44 (in housing), IP55 (with accessory)
VdS classF
VdS-NrG 205002
DimensionsW: 133 mm H: 133 mm D: 36 mm

Declaration of Performance

TypeNameSize
DoP-IQ8mcp Bus Detector manual call point_804905_07.2013 2 MB