VESDA-E VEU with LEDs, esserbus

VEP-A00-EBTI

Like VEU-A00 but with an integrated esserbus® transponder for direct integration into the esserbus® loop
Certified for requirements to EN 54-20 for classes A, B and C:
• max. 80 pipe holes for class A
• max. 80 pipe holes for class B
• max. 100 pipe holes for class C
Operating voltage
18 - 28V DC
Quiescent current
@ 24 V DC ca. 625 mA
Alarm current
@ 24 V DC ca. 740 mA (at 4 transponder groups)
Contact load relay
2 A @ 30 V DC NO/NC
Sensitivity
0.001% - 20% obs/m
Connection Terminal
0.2 - 2.5 mm²
Maximum pipe lengthn
800 m branched, 400 m single pipe
Monitoring area
1600 m² (6500 m²)
Type of protection
IP 40
Weight
ca. 5.37 kg
Dimensions
W: 350 mm H: 225 mm D: 135 mm