VESDA-E VEP 1 pipe with LEDs, esserbus

VEP-A00-1P-EBTI

Like VEP-A00-1P but with an integrated esserbus® transponder for direct integration into the esserbus® loop
Certified for requirements to EN 54-20 for classes A, B and C:
• max. 30 pipe holes for class A
• max. 40 pipe holes for class B
• max. 45 pipe holes for class C
Operating voltage
18-28V DC
Quiescent current
@ 24 V DC ca. 380 mA
Alarm current
@ 24 V DC ca. 492 mA (at 4 transponder groups)
Contact load relay
2 A @ 30 V DC NO/NC
Sensitivity
0.005% - 20% obs/m
Connection Terminal
0.2 - 2.5 mm²
Maximum pipe length
130 m branched, 100 m single pipe
Monitoring area
1000 m²
Type of protection
IP 40
Weight
ca. 4.47 kg
Dimensions
W: 350 mm H: 225 mm D: 135 mm