Analogue PVC Coated Sensor Cable

762251

Standard PVC cable for indoor installation for normal environmental conditions, also in high humidity, but without mechanical stress. The sensor cable must be fixed below ceiling areas at least every 50cm. The distance to cold ceiling areas must be at least 2 cm.

  • Structure is fully insulated, four-core twisted and foil shield with shielding wire
  • 1 kV insulation tested, PVC outer coating
  • 4.83 mm +/- 0.2 mm total wire diameter
  • 60 mm minimum bending radius
  • -40 °C minimum ambient temperature
  • The maximum ambient temperature depends on the selected alarm temperature
  • Minimum sensor cable length: 50 m - class A1I/A2I and 54°C alarm settings and 30 m - all other alarm settings (not EN 54-22)

Additional Information:
The indicated price is the price per meter. The minimum order quantity is 5 meters or a multiple thereof. Cancellation and return are excluded.

Ambient temperature
-40 °C ... 125 °C (relative humidity up to 99% at -40°C ... +40°C, from 40°C rel. humidity up to 75%)
Color
red (PVC)
Weight
approx. 25,6 g per m
Maximum sensor length
500 m