| Range |
max. 25 m110 ft /35 m (IR3), 25 m/80 ft (UV, UV/IR) alarming within 10 seconds to a 1 ft2(0.1 m2)n-heptane fire |
| Cone of vision |
90˚minimum horizontal and vertical |
| Power |
10-28 VDC (12-24 VDC nominal)
|
| Start up times |
<10 sec
|
| Alarm response time |
8 to 30 sec |
| Alarm output settings |
Selectable LEDs and relays latching/non-latching; factory setting: latching |
| Automatic & manual Self-Test |
Automatic Sensor Test (built in Self-Test) and manual Self-Test |
| Operating current normal |
25 mA at 24 VDC |
| Current in alarm, at 24 VDC |
±75 mA at 24 VDC |
| Housing |
Glass Reinforced Polyester (GRP), Non-incendive. UV resistant, Self-Extinguishing V–0 (UL-94) |
| Dimensions |
4.9 x 3.15 x 2.25 in (125 x 80 x 57 mm) |
| Weight |
1.05 lb (465 g)
|
| Temperature, operating |
–40 ˚F to +158 ˚F (–40 ˚C to +70 ˚C) |
| Ingress protection |
IP65 |
Detector specification
|
EN54-10, FM3260 |
| EC-type examination certificate |
ATEX Zone2/22, FM Class 1, 2 & 3 Div2 |