FAAST-LT double knock Loop based Aspiration Sampling Detector

MI-FL2012EI-HS

FAAST LT Aspirating Smoke Detector with two sensor and one channel to connect to the Honeywell Morley-IAS intelligent loop.Requires external power 24 V DC from EN54-4 PSU.
The FAAST LT Aspirating Smoke Detector is designed with the installer and end user in mind. It serves the wide variety of Class C applications where maintenance is difficult, other smoke detection methods are inappropriate or prone to fail due to harsh Environments or Areas where aestthetics matters. It is also suitablefor smaller Mission critical applications where very early warning - Class A or B detection is required.
FAAST LT combines proven aspiration detection technologies to deliver reliable smoke detection and efficient installation and maintenance. The device includes high sensitivity laser fire detection, ultrasonic flow sensors, and internal design features to protect vulnerable components from environmental and human threats.
The device is fast to install and easy to commission thanks to PIPE IQ LT pipe design and configuration software which is included as standard. FAAST LT loop based devices are available as single channel and dual channel devices, offering flexibility for different detection strategies. A range of customizable settings are geared towards maximizing device performance and meeting different application needs.
Loop capability allows standard device integration, maintenance and support consistent with all other Honeywell Morley-IAS loop devices.
The detector provides alarm and fault relays with auxiliary events relay as an option. These can be set as latched or non-latched. To accommodate local installation standards or environments, flow and general fault delays can also be set.
  • Multiple event logging up to 2240 events
  • Rotary decade address switches
  • Ultrasonic airflow sensing
  • PipeIQ™LT software provides intuitive system layout and configuration all in one package
  • User friendly air flow pendulum graph for verification of pipe network functionality
  • Protected electronics from air flow and accidental damage during installation or maintenance
  • Easily replaceable and reusable filter without affecting the rest of the device
  • Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no special tools required.
  • Easy access to parts requiring routine maintenance: filter(s) or sensors(s).
  • Single & Dual channel versions with independent channels including fan, sensor and flow monitoring
  • IP65 enclosure
  • Specifications: EN54-20, EN54-17
  • BRE approved
DimensionH: 403 mm W: 356 mm D: 135 mm
Weight6.5 kg
Relative humidity10 ... 93% (non-condensing)
Operating temperature-10°C ... 55°C
External supply voltage18.5 ... 31.5 V DC
Remote reset time1 sec.
Power reset0.5 sec.
Avg. operating current200 mA @ 24 V DC (excl. sounders)
Max. avg. operating current500 mA @ 24 V DC (excl. sounders)
IP ratingIP65
Sensitivity0.06% ... 6% obs/m